Programming 
Page D-122  890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
Functional Description 
The SLEW RATE LIMIT block obtains the setpoint from the output of the application, correctly scaled by the REFERENCE 
block. The rate of change limits are applied and the setpoint is then passed on for further processing. 
When the braking block determines that the internal dc link voltage is too high it issues a Hold signal. This causes the SLEW 
RATE LIMIT block to hold the setpoint at its current value. This typically lasts for only 1ms, time for the excess energy to be 
dumped into the dynamic braking resistor. 
 
SETPOINT
DECEL LIMIT
ACCEL LIMIT
HOLD SIGNAL
 
 
Note  If the drive is part of a common DC link/bus system set the ENABLE parameter to FALSE. This disables ramp-hold 
during deceleration on high link volts feature.