Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page D-183
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
3 : READY
4 : ENABLED
5 : F-STOP ACTIVE
6 : TRIP ACTIVE
7 : TRIPPED
92.23 REMOTE REV OUT SEQUENCING LOGIC BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
92.24 HEALTHY SEQUENCING LOGIC BOOL 0 : FALSE
1 : TRUE
TRUE ro Output
92.25 START DELAY SEQUENCING LOGIC REAL 0.000 to 30.000 s 0.000 s rw
92.26 FAN RUNNING SEQUENCING LOGIC BOOL 0 : FALSE
1 : TRUE
TRUE ro Output
93.01 ENABLE AUTO RESTART BOOL 0 : FALSE
1 : TRUE
FALSE rw
93.02 ATTEMPTS AUTO RESTART INT 1 to 10 5 rw
93.03 INITIAL DELAY 1 AUTO RESTART REAL 0.0 to 600.0 s 10.0 s rw
93.04 ATTEMPT DELAY 1 AUTO RESTART REAL 0.0 to 600.0 s 10.0 s rw
93.05 TRIGGERS 1 AUTO RESTART WORD 0000 to FFFF 0000 rw
93.06 TRIGGERS 1+ AUTO RESTART WORD 0000 to FFFF 0000 rw
93.07 INITIAL DELAY 2 AUTO RESTART REAL 0.0 to 600.0 s 0.1 s rw
93.08 ATTEMPT DELAY 2 AUTO RESTART REAL 0.0 to 600.0 s 0.1 s rw
93.09 TRIGGERS 2 AUTO RESTART WORD 0000 to FFFF 0000 rw
93.10 TRIGGERS 2+ AUTO RESTART WORD 0000 to FFFF 0000 rw
93.11 PENDING AUTO RESTART BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
93.12 RESTARTING AUTO RESTART BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
93.13 ATTEMPTS LEFT AUTO RESTART INT _ 5 ro Output
93.14 TIME LEFT AUTO RESTART REAL _.x 0.0 s ro Output
94.01 SEQ MODES LOCAL CONTROL ENUM 0 : LOCAL/REMOTE
1 : LOCAL ONLY
LOCAL/REMO
TE
rw