Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page D-189
8
9
10
11
B
C
D
1
2
3
4
5
6
7
E
101.11 REVERSE REFERENCE BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
101.12 LOCAL SETPOINT REFERENCE REAL _.xx 0.00 % ro Output
101.13 LOCAL REVERSE REFERENCE BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
101.14 REFERENCE REAL _.xx 0.00 % ro Output
101.15 FWIRE SETPOINT REFERENCE REAL _.xx 0.00 % ro Output
101.16 SPEED DEMAND REFERENCE REAL _.x 0.0 Hz ro Output
102.01 RUN STOP MODE REFERENCE STOP ENUM 0 : RUN RAMP
1 : COAST
2 : DC INJECTION
3 : STOP RAMP
RUN RAMP rw
102.02 STOP TIME REFERENCE STOP REAL 0.0 to 600.0 s 10.0 s rw
102.03 STOP ZERO SPEED REFERENCE STOP REAL 0.00 to 100.00 % 0.10 % rw
102.04 STOP DELAY REFERENCE STOP REAL 0.000 to 30.000 s 0.500 s rw
102.05 FAST STOP MODE REFERENCE STOP ENUM 0 : RAMP
1 : COAST
RAMP rw
102.06 FAST STOP LIMIT REFERENCE STOP REAL 0.0 to 3000.0 s 30.0 s rw
102.07 FAST STOP TIME REFERENCE STOP REAL 0.0 to 600.0 s 0.1 s rw
102.08 FINAL STOP RATE REFERENCE STOP REAL 1 to 4800 Hz/s 1200 Hz/s rw
103.01 SETPOINT REFERENCE JOG REAL -100.00 to 100.00 % 10.00 % rw
103.02 ACCEL TIME REFERENCE JOG REAL 0.0 to 3000.0 s 1.0 s rw
103.03 DECEL TIME REFERENCE JOG REAL 0.0 to 3000.0 s 1.0 s rw
105.01 STALL TIME STALL TRIP REAL 0.1 to 3000.0 s 120.0 s rw 3
105.03 STALL LIMIT TYPE STALL TRIP ENUM 0 : TORQUE
1 : CURRENT
2 : TRQ OR CURRENT
TRQ OR
CURRENT
rw
108.01 ADVANCE PHASE INCH BOOL 0 : FALSE
1 : TRUE
FALSE rw
108.02 RETARD PHASE INCH BOOL 0 : FALSE
1 : TRUE
FALSE rw