890SD Standalone Drive 
Page 5-12  890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
Key to Wiring Diagram 
A 
Analog Clean Earth 
This must be insulated from the back panel. Analog reference X12/01 or digital reference 
X14/04 must be connected to this busbar, avoiding earth loops. 
B 
Back-plate  Earth the backplate to the star point (G). 
C 
Cubicle 
The 890 must be mounted inside a cubicle complying with the European safety standards 
VDE 0160 (1994)/EN50178 (1998).  
D 
Control Wiring 
Control terminals are SELV (Safe Extra Low Voltage), i.e. double-insulated from power 
circuits. 0.08mm
2
 (28AWG) to 2.5mm
2
 (12AWG). 
E 
Dirty Earth  This must be insulated from the back panel. It is used for all power earths. 
F 
Filter (optional) 
Refer to Chapter 6: "Associated Equipment" for the specified filter. This may help to 
achieve EMC compliance. Refer to Appendix C. 
G 
Star Point Earth/Ground 
The star point connects all earth busbars. Connect the star point to the incoming safety 
earth (PE). Note the possible requirement for PE2 connections to each drive, refer to page 
4-9. 
H 
Brake Resistor 
(DC+, EXT: frames B & C)
(DBR+, DBR-: frame D) 
External brake resistors are available. Refer to Chapter 6: "Associated Equipment". 
Ensure wiring is rated for highest system voltage. (890SD Frame D units also have 
internal brake resistors.)