890SD Standalone Drive
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page 5-15
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
Power Connections - 890SD Standalone Drive
SUPPLY MOTOR
SUPPLY
L1 L2 L3
MOTOR
M1 M2 M3
L1, L2, L3
Connect 3-phase supply in any order.
Maximum wire sizes:
Frame B: 6mm
2
/ 10AWG, 0.5-0.9Nm / 0.4-0.7lbf
Frame C: 10mm
2
/ 8AWG, 1.2Nm / 0.9lbf
Frame D: 16mm
2
/ 4AWG, 2-4Nm / 1.5-3lbf
M1 (U), M2 (V), M3 (W).
Connect to the motor in any order.
Maximum wire sizes:
Frame B: 6mm
2
/ 10AWG, 0.5-0.9Nm / 0.4-0.7lbf
Frame C: 10mm
2
/ 8AWG, 1.2Nm / 0.9lbf
Frame D: 16mm
2
/ 4AWG, 2-4Nm / 1.5-3lbf
DC+ / DC- Bottom Terminals - Option
DC+ DC-
These terminals can be used for link monitoring and for link
sharing between 890SD drives - caution: refer to the Link Shairing
Application note for limitations.
Use correctly rated wire - refer to Appendix E.
Maximum wire sizes:
Frame B: 6mm
2
/ 10AWG, 0.5-0.9Nm / 0.4-0.7lbf
Frame C: 10mm
2
/ 8AWG, 1.2Nm / 0.9lbf
Frame D: 16mm
2
/ 4AWG, 2-4Nm / 1.5-3lbf