Installer Manual Fleck 5810 - SXT - Programming
66 / 106 Ref. MKT-IM-016 / C - 08.06.2018
6.5.13.3 For regeneration type O-UF and O-DF
Note
The regeneration cycles are identified as C1 to C20.
Mandatory
The last cycle must be set with LC.
6.5.14. Day of the week (Dn, n = 1 to 7)
Set the active days for regeneration.
Note
The day of week parameter is only available if day of the week mode has been set in
regeneration control type selection.
Note
The current day is defined from D1 (Monday) to D7 (Sunday).
Note
By default, every Dn is set to OFF.
AE Press or to set the type of regeneration cycle.
AF Press to validate the selection.
AG Press or to set the duration of this cycle.
AH Press to validate the selection and move to the next regeneration
cycle.
AI Repeat AE to AH as needed.
AJ Select LC.
AK Press to validate the selection and to move to the next parameter.
In this example:
C1 = Rapid Rinse
for 30 min
AL Press or to set "ON" or "OFF" to set the day as a regeneration day.
AM Press to validate the selection.
AN Repeat AL to AM until D7 is set.
AO Press to validate the selection and move to the next parameter.

Table of Contents

Other manuals for Pentair FLECK 5810 SXT

Related product manuals