Installer Manual Fleck 5810 - SXT - Programming
Ref. MKT-IM-016 / C - 08.06.2018 69 / 106
6.5.18.2 Relay end time (ET)
Set the relay end time.
Note
This option is available only if time based relay (RE) is set to tb.
Note
The relay end time can be set from start time +1, to the total regeneration durations.
6.5.19. Flow based relay setting (VR)
Select the relay setting.
Note
The relay can bet set upon a time base (tb) or a flow base (Fb). Only one method can be used
at a time.
Note
This option is available only if time based relay (RE) is set to OFF.
Note
If set to Fb, the controller will enable and disabled the relay output every time the set volume
interval is reached for the set time ON.
AX Press or to set the relay start time.
AY Press to validate the selection and move to the next parameter.
AZ Press or to set the relay end time.
BA Press to validate the selection and move to the next parameter.
BB Press or to select between Fb and OFF.
BC Press to validate the selection and move to the next parameter.