Preconditions for installation and use
Compass 4SCompass 2S
IP 66IP code (NEN-EN-IEC 60529)
0 … 35 °CPermitted ambient temperature during
normal operation
10 … 95 % (non-condensing)Permitted ambient relative humidity
during normal operation
2 (normal, non-conducting pollution)Pollution factor (NEN-EN-IEC 61010-1)
-25 … 70 °CPermitted temperature for transport
and storage
0 … 95 % (non-condensing)Permitted ambient relative humidity
for transport and storage
50 °CMaximum temperature inside cabinet
during normal operation
75 W at maximum permitted ambient
temperature (active cooling is required
if more heat is generated)
57 W at maximum permitted ambient
temperature (active cooling is required
if more heat is generated)
Maximum heat generated in cabinet
on the wall using four mounting holes
using 4 M8 bolts (minimum length 5 cm) (not included)
Installation
do not expose to direct sunlightOther installation and environmental
requirements
do not install close to a heat source or outdoors
2000 meters above sea levelMaximum installation height
IIInstallation category
Installing Priva Compass - 00.014122