Do not use aggressive cleaning and/or abrasives.
Make sure that no moisture, dirt or dust enters the housing when opening the Outside
temperature sensor. This can negatively impact the measurement.
The item 'Temp.sensor 6x60 (glass)' (Part number 111070) is available for replacing a defective
sensor.
Specifications
Outside temperature sensorArticle description
3779204Article number
NTC - 3000 Ω/25 °CMeasuring principle
0,1 °CResolution
0,2 °C, at temperatures between 0 and 40 °C
0,5 °C, at temperature < 0 °C or > 40 °C
Measurement accuracy
-40 °C .. +80 °CRange
55 sResponse speed (T63%)
Discharges 900 V/100 nFProtection