Universal input - Other
250 VFunctional isolation of inputs in relation to system
neutral
10 AMaximum current of FG connections
Indication (for modules with manual override or
indication only)
green/red LEDs for status of inputs for digital use (colour is
adjustable)
Analogue outputs
0 10 VOutput voltage control range
5 mAMaximum load current supplied per output
(source)
Maximum current load drawn per output (sink)
> 2 kΩLoad resistance
600 µV (> 13 bits over 10 V)Resolution
± (10 mV + 0.5% of the control signal)Accuracy
± 150 mVAccuracy of feedback
200 ms (to 70% of the set value)Adjustment time
maximum 5 µAInput leakage current with high impedance
output¹
output is short-circuit proof (self-restoring after a brief short
circuit/overload)
output is protected against ± 30 VDC and 30 VAC
Protection
5Number of switch-on attempts in the event of
short circuit or overload²
250 VFunctional isolation of outputs in relation to
system neutral
10 AMaximum current of FG connections
Indication (for modules with manual override only)
orange LEDs for indication of output voltage
orange LED for status of control (automatic or manual)
buttons to set the voltage level of the output manually:
Controls (for modules with manual override only)
+: manually increase output voltage
A: automatic control of output voltage
-: manually decrease output voltage
¹ The output is high impedance ex-factory; the module has not yet been configured then. In addition, unused
outputs and the outputs where the overload protection has been activated are high impedance.
² After a short-circuit or overload the output is switched back on after 0.5 s. The output switches back off
immediately if the overload is still present. The output performs a maximum of 5 switch-on attempts with a time
interval of 0.5 seconds. After 5 attempts, the output is switched off and manual intervention is required.
133Installing Priva Compass - 00.014