Universal input - Other
250 VFunctional isolation of inputs in relation to system
neutral
10 AMaximum current of FG connections
Indication (for modules with manual override or
indication only)
• green/red LEDs for status of inputs for digital use (colour is
adjustable)
Analogue outputs
0 … 10 VOutput voltage control range
5 mAMaximum load current supplied per output
(source)
Maximum current load drawn per output (sink)
> 2 kΩLoad resistance
600 µV (> 13 bits over 10 V)Resolution
± (10 mV + 0.5% of the control signal)Accuracy
± 150 mVAccuracy of feedback
200 ms (to 70% of the set value)Adjustment time
maximum 5 µAInput leakage current with high impedance
output¹
output is short-circuit proof (self-restoring after a brief short
circuit/overload)
output is protected against ± 30 VDC and 30 VAC
Protection
5Number of switch-on attempts in the event of
short circuit or overload²
250 VFunctional isolation of outputs in relation to
system neutral
10 AMaximum current of FG connections
Indication (for modules with manual override only)
• orange LEDs for indication of output voltage
• orange LED for status of control (automatic or manual)
buttons to set the voltage level of the output manually:
Controls (for modules with manual override only)
• +: manually increase output voltage
• A: automatic control of output voltage
• -: manually decrease output voltage
¹ The output is high impedance ex-factory; the module has not yet been configured then. In addition, unused
outputs and the outputs where the overload protection has been activated are high impedance.
² After a short-circuit or overload the output is switched back on after 0.5 s. The output switches back off
immediately if the overload is still present. The output performs a maximum of 5 switch-on attempts with a time
interval of 0.5 seconds. After 5 attempts, the output is switched off and manual intervention is required.
133Installing Priva Compass - 00.014
General specifications of Priva Blue ID C-Line controllers and modules