5.5 Internet connection problems
The Redback inverter will perform best when it is permanently connected to the internet. An internet connection enables the
inverter to send data to the Redback cloud, where you can use the Redback app or portal to view performance and fine tune
the system.
Occasionally, the inverter may lose internet connection and be reported as “offline”. Ethernet connected systems usually self-
repair after a system restart. Wi-Fi problems usually require that the installation details be updated.
The most common causes of “offline” reports are:
INDICATION
CONNECTION AFFECTED
REMEDY
Ethernet
Wi-Fi
Change of Internet Service Provider e.g., Telstra,
Optus, TPG, Dodo etc
Ethernet: Restart the system
Wi-Fi: Restart and re-onboard
New router or modem
Change of Network name or SSID
Change settings in ADSL modem
Changed Wi-Fi or Network password
Wi-Fi: Restart and re-onboard
Too many users or devices on your home Wi-Fi
network
Limit users or devices; upgrade Wi-Fi router;
connect using ethernet.
Wi-Fi signal is weak or variable due to obstructions
or distance between the inverter and your Wi-Fi
router’s antenna.
Experiment with Wi-Fi router locations; use a
Wi-Fi extender; connect using ethernet.
Attempting connection to a 5Ghz Wi-Fi network
This equipment is not compatible with 5Ghz Wi-Fi
networks. Use a 2.4Ghz network or ethernet.
5.6 Inverter unexpected shutdown
The inverter may shut down or isolate itself from the grid if it detects conditions that may cause damage to the inverter or
batteries; or create an unsafe situation. Incident causes can be diagnosed by examining the data available on the portal.
Unexpected shutdowns may occur in the following circumstances:
CAUSE
RELEVANT CHARTS FOR
DIAGNOSIS (IN PORTAL)
COMMENT
Continuous backup circuit load
exceeds 4600W.
Backup Load- Power
May occur when too many devices are active on the
backup circuit.
Backup circuit load exceeds 6900W for
more than 10 seconds.
Backup Load- Power
May occur when too many high current appliances are
used simultaneously
, or when a large load starts up, such
as a pump.
Backup load exceeds available Battery
+ Solar power.
Backup Load- Power
Battery
- Power
PV- Power
If internal temperature is greater than
60°C.
Inverter- Temperature
Battery Cabinet-Temp.
Output is reduced above 45°C.
Grid supply did not comply with local
or DNSP requirements.
Grid- Voltage
Grid
- Frequency
Grid
- Status
Check Region setting is correct.
Check voltage
-drop calculations.
Tap setting on trans
former may be incorrect. Contact
DNSP.
The
EMS and backup circuit will operate if power is
available from PV or batteries.