Chapter 1 Installation/Wiring
Alternative Accel/Decel rates can be made through digital inputs,
communications and/or parameters. See below for the override priority.
(1) Setting is specific to PowerFlex 525 drives only.
Purge Input Enabled
AND Active
Terminal Block Jog
Input Enabled AND
Active
Input(s) is
programmed as
Acc/Dec
(2/3/4)
Is speed controlled
by [Preset Freq x]
Active
[Speed Referencex]
= Comms
and
[Start Source x]
= 3 “Serial/DSI” or
4 “Network Opt” or
5 “EtherNet/IP”
Active
[Speed Referencex]
= 13 (Step Logic)
(1)
Drive stopped
(NOT running)
Accel/Decel always
Accel/Decel 1.
Accel/Decel from
[Jog Acc/Dec].
Accel/Decel 2 is active
when input is selected
by Accel and Decel input.
Drive uses Accel 1
and Decel 1.
No
No
No
No
No
No
No
Yes
Yes Yes
Yes
Yes
Yes
Yes
Accel/Decel 1/2/3/4 is
selected by the default
[Preset Freq x] setting.
Accel/Decel 1 or 2 is
selected according
to Comms.
Accel/Decel 1/2/3/4 is
selected according to
Step Logic
Active [DigIn TermBlk xx]
= 32 (Sync Enable)
[Sync Time] is used
for Accel/Decel rate
No
Yes
Traverse active if
[Max Traverse] > 0 Hz
Traverse Inc/Dec
is used for
Accel/Decel rate
No
Yes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PowerFlex 520 Series and is the answer not in the manual?

Rockwell Automation Allen-Bradley PowerFlex 520 Series Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PowerFlex 520 Series
CategoryDC Drives
LanguageEnglish

Related product manuals