Rockwell Automation Publication 2198-RM003B-EN-P - November 2020 21
Chapter 2 Replacement Considerations
Table 14 - Ultra3000 (400V-class) Drives Power Specifications
Attribute 2098-DSD-HV030 2098-DSD-HV050 2098-DSD-HV100 2098-DSD-HV150 2098-DSD-HV220
AC input voltage
(1) (2)
230…480V rms, three-phase
AC input Frequency 47…63 Hz
Main AC input current
(3) (4)
460V AC (rms) nom
460V AC (rms) max inrush
4 A
6 A
7 A
6 A
14 A
6 A
20 A
6 A
28 A
6 A
Auxiliary AC input current
230V AC (rms) nom
360V AC (rms) nom
480V AC (rms) nom
230V AC (0-pk) max inrush
(5)
480V AC (0-pk) max inrush
(5)
0.55 A
0.35 A
0.25 A
47 A
68 A
Continuous output current (rms) 5.0 A 7.8 A 16.3 A 24.0 A 33.2 A
Continuous output current (0-pk) 7.0 A 11 A 23 A 34 A 47 A
Peak output current (rms) 9.9 A 15.6 A 32.5 A 48.1 A 66.5 A
Peak output current (0-pk) 14 A 22 A 46 A 68 A 94 A
Bus capacitance 470 µF 705 µF 940 µF 1880 µF
Internal shunt resistance 120 40 25 20
Shunt on
230V AC input
480V AC input
400V DC
800V DC
Shunt off
230V AC input
480V AC input
375V DC
750V DC
Bus overvoltage
230V AC input
480V AC input
410V DC
810V DC
Internal shunt
Continuous power
Peak power
100 W
5.3 kW
200 W
16 kW
200 W
25.6 kW
400 W
32 kW
External shunt
Resistance (-0/+5%)
Continuous power
Peak power
120
3 kW
5.3 kW
40
10 kW
16 kW
25
15 kW
25.6 kW
20
22 kW
32 kW
Energy absorption capability
230V AC input with 230V motor
230V AC input with 460V motor
480V AC input
15 J
129 J
55 J
22 J
194 J
82 J
29 J
259 J
109 J
59 J
517 J
219 J
Continuous power output
230V AC input
480V AC input
1.5 kW
3.0 kW
2.5 kW
5.0 kW
5.0 kW
10 kW
7.5 kW
15 kW
11 kW
22 kW
(1) Specification is for nominal voltage. The absolute limits are ±10%, or 207…264V rms and 324…528V rms.
(2) The 2098-DSD-HVxxx-xx drives can be powered with 230V rms and used with motors designed for 230V operation. In such cases, the voltage levels used for shunting and DC bus
overvoltage limits are adjusted to be compatible with the voltage limit of the motor.
The 2098-DSD-HVxxx-xx drives can be powered with 480V rms and used with motors designed for 480V operation. In such cases, the voltage levels used for shunting and DC bus
overvoltage limits are adjusted to be compatible with the voltage limit of the motor.
(3) The 2098-DSD-HVxxx -xx (400V-class) drives are limited to three contactor cycles per minute.
(4) Power initialization requires a short period of inrush current (processor controlled via soft start circuitry). Dual element time delay (slow blow) fuses are recommended.
(5) 400 s half wave sine.