Reference Manual
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
F-4
RESTART 16 Allows a manual restart to be initiated. Several degrees of restart are possible:
1 Run: Nominal state when not restarting
2 Restart resource: Not used
3 Restart with defaults: Set parameters to default values (see
START_WITH_DEFAULTS below for which parameters are set).
4 Restart processor: Does a warm start of the central processing unit (CPU).
RS_STATE 07 RS_STATE denotes the state of the function block application state machine.
SAVE_CONFIG_NOW 61 This parameter controls saving of configuration in EEPROM.
SAVE_CONFIG_BLOCKS 62 Number of EEPROM blocks that have been modified since the last burn. This value
will count down to zero when the configuration is saved.
SECURITY_IO 65 SECURITY_JUMPER denotes the status of security jumper/switch.
SELF_TEST 59 SELF_TEST instructs the resource block to perform a self-test.
SET_FSAFE 29 Allows the FAULT_ STATE condition to be manually initiated by selecting Set.
SHED_RCAS 26 This parameter represents the time duration at which to give up on computer writes
to function block RCas locations.
SHED_ROUT 27 This parameter represents the time duration at which to give up on computer writes
to function block ROut locations.
SIMULATE_IO 64 SIMULATE_JUMPER shows the status of the simulate jumper/switch.
SIMULATE_STATE 66 SIMULATE_STATE represents the state of the simulate function.
ST_REV 01 The revision level of the static data associated with the function block. The revision
value will be incremented each time a static parameter value in the block is
changed.
START_WITH_DEFAULTS 63 START_WITH_DEFAULTS controls what defaults are used at power-up.
STRATEGY 03 The strategy field can be used to identify grouping of blocks. These data are not
checked or processed by the block.
SUMMARY_STATUS 56 This parameter represents an enumerated value of repair analysis.
TAG_DESC 02 The user description of the intended application of the block.
TEST_RW 08 A parameter for a host to use to test reading and writing. Not used by the device at
all.
UPDATE_EVT 35 This alert is generated by any change to the static data.
WRITE_ALM 40 This alert is generated if the write lock parameter is cleared.
WRITE_LOCK 34 If set, no writes from anywhere are allowed, except to clear WRITE_LOCK. Block
inputs will continue to be updated.
WRITE_PRI 39 WRITE_PRI represents the priority of the alarm generated by clearing the write
lock.
XD_OPTION 44 Indicates which transducer block licensing block options are enabled.