IQ3 Full Configuration Manual – Section: Data Log 55
4.4.2 Operation Logs – Statistics
Open Limit
Operation Logs
Starts Profile
Statistics
Service Log
Bluetooth Log
Stopped
Temperature
Maximum C 32
Date 16:35:03 22/04/2013
Minimum C 0
Minimum Time 13:14:07 22/04/2013
Torque
Max Opening 18
Date 16:57:33 20/03/2013
1/24
Statistics
This screen displays statistics of actuator operation. Date and
times are only accurate if the date/time is set locally as per
section 4.6.
To scroll through the statistics log use
and .
Temperature
1/24 Maximum C - Displays the maximum temperature the
internal enclosure has reached in degrees Celsius.
2/24 Date - Displays the date and time that the internal
enclosure reached the maximum temperature.
3/24 Minimum C - Displays the minimum temperature the
internal enclosure has reached in degrees Celsius.
4/24 Date - Displays the date and time that the internal
enclosure reached the minimum temperature.
Torque
5/24 Max Opening - Displays the maximum opening torque the
actuator has reached.
6/24 Date - Displays the date and time that the actuators
maximum opening torque was reached.
7/24 Max Closing - Displays the maximum closing torque the
actuator has reached.
8/24 Date - Displays the date and time that the actuators
maximum closing torque was reached.
9/24 Ave. Torque % - Displays the actuators average torque as
a percentage.
Power
10/24 Motor Run Time - Displays the total motor running time.
11/24 On Battery - Displays the total time the actuator has
been on battery power.
12/24 Max On Time - Displays the maximum time the actuator
has been powered on.
13/24 Max Off Time - Displays the maximum time the actuator
has been powered off.
14/24 Power Ups - Displays the total number of times the
actuator has been powered up.
Counts
15/24 Clock - Displays the current date and time (if set locally as
in section 4.6).
16/24 Total Turns - Displays the total number of actuator turns.
17/24 Max Starts/Hr - Displays the maximum number of motor
starts that occurred in an hour.
18/24 Date - Displays the date and time that the maximum
number of motor starts occurred.
19/24 Open Starts - Displays the total number of motor starts
in the open direction.
20/24 Close Starts - Displays the total number of motor starts
in the closed direction.
Trips
21/24 Last Open Limit - Displays the date and time the
actuator last reached its open limit.
22/24 Last Close Limit - Displays the date and time the
actuator last reached its closed limit.
23/24 Open Reset Time - Displays the date and time the
actuator last moved away from the open limit.
24/24 Cls. Reset Time - Displays the date and time the actuator
last moved away from the closed limit.