II.USERS
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 20/40
5-4-5. WAIT
Select WAIT at the Program page(Figure 5-4-1) for switching the WAIT page.
Figure 5-4-12 WAIT
① WAIT USE : Set ON/OFF for using WAIT. All patterns are under WAIT function.
② TEMP ZONE : Set a TEMP ZONE.
③ HUMI ZONE : Set a HUMI ZONE.
④ WAIT TIME : Set a WAIT TIME
(Table 5-6) WAIT PARAMETER
Name Function Valid Range Unit Default Value
WAIT USE WAIT USE OFF, ON ABS OFF
TEMP ZONE TEMP WAIT ZONE T.EUS(0 ~ 100%) T.EUS T.EUS(0%)
HUMI ZONE HUMI WAIT ZONE H.EUS(0 ~ 100%) H.EUS H.EUS(0%)
WAIT TIME WAIT TIME 00.00 ~ 99.59 ABS 00.00
☞ Ex) Wait
If T.SP=90℃, wait area(TEMP.ZONE)=5℃ then, wait zone is 85℃~95℃. When WAIT TIME=1H; PV
reach the wait area before WAIT TIME, work next segment, PV dose not reach the wait area before
WAIT TIME, it is waiting during WAIT TIME then go to next segment. It is or condition both of
TEMP.ZONE and HUMI.ZONE.
Figure 5-4-13 WAIT
3SEG1SEG
95°
T.ZONE
T.ZONE
C
90°
85°
WAIT TIME=1H
2SEG
C
C
T.SV
T.PV
Wait time
2 SEG Working time