III : COMMUNICATION
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 14/21
4.2 Functions
FUNCTION is consisted D-Register for operation.
■ PROGRAM running D-Register
D-Reg. Symbols Descriptions
D0100 SET_PTNO Set program pattern number
D0121 WAITMD Set using WAIT function
D0122 TEMP_WZ Set wait zone of temperature
D0123 HUMI_WZ Set wait zone of humidity
D0124 WAIT_TM Set wait time
■ FIX running D-Register
D-Reg. Symbols Descriptions
D0102 FIX_T_SP Set temp SP on FIX running
D0103 FIX_H_SP Set humi SP on FIX running
D0110 OTMSL Set using OP TIME(0:OFF, 1:ON)
D0111 OTM_H Set the hour for FIX OP TIME
D0112 OTM_M Set the min for FIX OP TIME
■ Operation D-Register
D-Reg. Symbols States Value Descriptions
RUN 1 PROG/FIX RUN
HOLD 2 HOLD ON/OFF
STEP 3 SEGMENT STEP
D0102 MODE
STOP 4 PROG/FIX STOP
PROG 0 PROG MODE SETTING
D0104 OPMODE
FIX 1 FIX MODE SETTING
STOP 0 STOP MODE SETTING
COLD 1 COLD MODE SETTING
D0105 PWRMODE
HOT 2 HOT MODE SETTING
For PROG RUN's (or FIX RUN) through communication,
TEMI 770 must be STOP(PROG STOP/FIX STOP).
Ex) TEMI 770 should be PROG STOP(D0104 = 0001, D0102 = 0004)
for switching FIX RUN TO PROG RUN.