IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 30/40
5-6-4. PID SETTING
Select PID at the SETUP page(Figure 5-6-1) for switching the PID page.
5-6-4-1. TEMP PID(Temp)
Figure 5-6-9 TEMP PID
TEMP REFERENCE(T1/T2)
: Set the boundary value about temp span of PID zone.
AUTO TUNING GROUP
: Go to the PID Group for PID(1~9) for change the PID value.
HYSTERESIS
: Set the HYSTERESIS when select PID zone.
DISPLAY PRESENT RUNNING PID No.
Ex) Auto Tuning can be doing only on Fix running, Auto Tuning is doing with SP and
the result will be saved automatically on the zone which is for SP.
Tuning point : Refer Tuning point on HUMI PID for detail function.
HRL < HSP < H1 & T.RL NSP < T1 than
PID GROUP 1
T1 NSP < T2 than
PID GROUP 4
T2 NSP < T.RH than
PID GROUP 7
H1 < HSP < H2 & T.RL NSP < T1 than
PID GROUP 2
T1 NSP < T2 than
PID GROUP 5
T2 NSP < T.RH than
PID GROUP 8
H2 < HSP < H.RH & T.RL NSP < T1 than
PID GROUP 3
T1 NSP < T2 than
PID GROUP 6
T2 NSP < T.RH than
PID GROUP 9
NSP=0 Æ Saved PID GROUP1, NSP=100 Æ Saved PID GROUP 9
(Table 5-10) TEMP TUNE PARAMETER
Name Function Valid Range Unit Default Value
T1 TEMP REFERENCE 1 T.EU (0~100%) T.EU T.EU (0%)
T2 TEMP REFERENCE 2 T.EU (0~100%) T.EU T.EU (0%)
RHY HYSTERESIS BAND T.EU (0~10%) T.EU T.EU (0.5%)
TUNING POINT AT TUNING POINT T.EUS (0.01~1.00%) T.EUS T.EUS(0.1%)
Go to HUMI TUNE page (Figure 5-6-9)