II.USERS
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 32/40
5-6-4-3. PID GROUP(PID1~PID9)
Figure 5-6-11 PID SET
OH.OL
: The range of controlled output
Ex) OH.OL (OL < OH)
(Table 5-12) PID(PID1~PID9) PARAMETER
Name Function Valid Range Unit Default Value
P PROPORTIONAL BAND 0.1 ~ 999.9 ABS 5.0
I INTEGRAL TIME 0 ~ 6000 ABS 60
D DERIVATIVE TIME 0 ~ 6000 ABS 240
T.OH TEMP OUT LIMIT HIGH 0.0 ~ 100.0 ABS 100.0
T.OL TEMP OUT LIMIT LOW 0.0 ~ 100.0 ABS 0.0
H.OH HUMI OUT LIMIT HIGH 0.0 ~ 100.0 ABS 100.0
H.OL HUMI OUT LIMIT LOW 0.0 ~ 100.0 ABS 0.0
PID1~PID9
105%
-5%
OL
OH
Controlled Range
0% 100%