Historic Logging
Running—Starts the historic log but does not affect ash memory logging, status point
log entries, or special events logging.
StoppedStops the historic log but does not affect ash memory logging, Status Point
Log entries, or special events logging (Subsequent events will not be put into the historic
log, preventing newer events from overwriting older events. Be sure to return the Historic
Logging mode to the Running setting so future events will be logged.)
Clear History Log
This button clears all data in the historic log. It does not affect ash memory logging,
status point log entries, or special events logging. The date and time of the last Clear
History Log command are displayed. Clearing the historic log permanently deletes all
event data. If event data should be preserved, generate an HTML report of logged data
before clearing the log.
Chronological Browsing (static – no refill)
Chronological browsing is only available in the Static View mode. It is not available in
the Real Time View mode. Because the size of the Logs>Historic Log screen is only a
fraction of the historic event log, the historic event log must be navigated chronologically,
either by Browse By Time mode or Browse By Page mode.
Browse By Time
This loads up to 160 events that occurred at or after the specic time entered. Only
events that satisfy the event categories criterion are placed in the Logs>Historic Log
screen. If all events in the historic event Log occurred before the specied time, the
oldest-available events are placed in the Logs>Historic Log screen. The Logs>Historic
Log screen is relled as soon as the specic time is entered; the specied time is cleared
when the rell is complete.
Browse By Page
Historic log pages can be browsed four ways:
Oldest 8 PagesLoads up to 160 of the oldest-qualifying events from the historic event
log
Newest 8 PagesLoads up to 160 of the newest-qualifying events from the historic
event log
Previous 8 PagesLoads up to 160 previous events relative to the events currently in
the Logs>Historic Log screen
Next 8 PagesLoads up to 160 next events relative to the events currently in the
Logs>Historic Log screen
When the selection is entered, the Logs>Historic Log screen is refilled immediately.
Because the historic event log is circular, selecting the Previous 8 Pages option may
cause the newest events to be displayed (if the Logs>Historic Log screen presently holds
the oldest). Similarly, selecting the Next 8 Pages option may cause the oldest events to
be displayed (if the Logs>Historic Log screen presently holds the newest)
Wave Form Capture
Click on this button to trigger a waveform capture to be stored in the compact ash
memory. Select the Tools>Compact Flash Access options on the menu to retrieve the
le.
S&C Instruction Sheet 766-530 177
Log Management

Table of Contents

Other manuals for S&C IntelliRupter PulseCloser

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the S&C IntelliRupter PulseCloser and is the answer not in the manual?

S&C IntelliRupter PulseCloser Specifications

General IconGeneral
BrandS&C
ModelIntelliRupter PulseCloser
CategoryIndustrial Electrical
LanguageEnglish

Related product manuals