S&C Instruction Sheet 461-509 35
Table 2. Import and Export Settings ConfigurationContinued
Parameter Group Attribute Description
Data
Type
Range of Value
<AnalogInputSetPoints>
<analoginputsetpoint/>
</AnalogInputSetPoints>
statuspoint See Status Point on DNP3 Outstation Settings screen. Integer 0…20
codedescription See Code Description on DNP3 Outstation Settings screen. Integer
Per S&C
Instruction Sheet
461-560
eventclass
See Class on DNP3 Outstation Settings screen. A value of 0
corresponds to NO EVENT.
Integer 0,1,2,3
fixeddeadband
See Fixed Deadband on DNP3 Outstation Settings screen.
Set to ‘disabled’ to disable fixed deadband reporting for this
setpoint.
Integer or
“disabled”
Any non-negative
integer value or
“disabled”
percentdeadband
See Pct Deadband on DNP3 Outstation Settings screen. Set
to “disabled” to disable percent deadband reporting for this
setpoint.
Integer or
“disabled”
Any non-negative
integer value or
“disabled”
scaling
Floating point scaling factor, to be applied as a multiplication
factor to the raw setpoint measurement before it is sent to the
SCADA master. See Scaling on DNP3 Outstation Settings
screen.
float 0.001 … 1000
<CounterSetPoints>
<countersetpoint/>
</CounterSetPoints>
statuspoint See Status Point on DNP3 Outstation Settings screen. Integer 0 … 19
codedescription See Code Description on DNP3 Outstation Settings screen. Integer
Per S&C
Instruction Sheet
461-560
eventclass
See Class on DNP3 Outstation Settings screen. A value of 0
corresponds to NO EVENT.
Integer 0,1,2,3
fixeddeadband
See Fixed Deadband on DNP3 Outstation Settings screen.
Set to “disabled” to disable fixed deadband reporting for this
setpoint.
Integer or
“disabled”
Any non-negative
integer value or
“disabled”
percentdeadband
See Pct Deadband on DNP3 Outstation Settings screen. Set
to “disabled” to disable percent deadband reporting for this
setpoint.
Integer or
“disabled”
Any non-negative
integer value or
“disabled”
<BinaryOutputSetPoints>
<binaryoutputsetpoint/>
</BinaryOutputSetPoints>
statuspoint See Status Point on DNP3 Outstation Settings screen. Integer 0 … 8
codedescription See Code Description on DNP3 Outstation Settings screen. Integer
Per S&C
Instruction Sheet
461-560
Retry Behavior
Will either discard the retry attempt or retry for the set interval
and number of attempts.
Binary Discard or Queue
Retry Interval Time, in seconds, between retry attempts. Integer 1 to 3600
Max Retry Attempts The maximum number of times the output will be retried. Integer 1 to 2,592,000