EasyManua.ls Logo

SBC PCD7.LR P5 Series - Page 86

SBC PCD7.LR P5 Series
137 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG Communication
5
5-10
RS-485 interfaces (ports 0 + 1) in general
Example 1:
What is the resource requirement for a network with a PCD7.LRxx-P5 room
controller with one:
1 HVAC (for one zone) room template application
1 PCD7.LRxx-P5 room controller
2 PCD1.E1000-A10 digital inputs
2 PCD1.A1000-A20 digital outputs
2 PCD1.A2000-A20 digital outputs
2 PCD1.G2200-A20 digital inputs and outputs
2 PCD1.W5200-A20 analogue outputs
E-Line FBoxes Registers Flags Program
size
Size of RAM
data blocks
DB RAM Non-
volatile
data
(inash)
[Byte] [Byte] [Flags or
registers]
One HVAC
room template
700 500 35404 250
EL + S-Bus master 196 119 2188 2064 2
2 PCD1.A1000
108 248 14024 336 2
2PCD1.A2000
80 180 11944 240 2
2PCD1.G2200
152 124 15432 416 2
2 PCD1.W5200
188 164 13776 344 2
2 PCD1.E1000
84 90 5496 120 2
Necessary resources 1508 1425 98264 3520 12 250
% usage of
PCD7.LRxx-P5
38% 36% 77% 35% 12% 25%
In this example, for one zone with 10 E-Line RIOs, the critical resource would be
the program size, where only approximately 20 kB of the user program is left for



Table of Contents

Related product manuals