16.9 Modbus master settings
If data from several segments is used, each segment requires at least one telegram.
When setting the correct byte sequence with values in IEEE and LONG format
the maximum permissible telegram length is 256 bytes, including the header and trailer
bytes.
16.10 Diagnosis and Troubleshooting
If one of the Fieldbusses has been activated (selected), every fault will be registered by the
‘’Communication Host’ (S9) event message if this message has not been assigned the event
class IG(NORE). The message is visible in the display and in EasyServe. If you only have a
display available, please read the following section. The EasyServe tool can assist in
providing more information for error diagnosis.
Meaning of the ‘Communication Host’ S9 event message
The event message is a group message for all errors concerning the Fieldbus connection.
These are:
n
Different station addresses are sent to the master and scales.
n
Different baud rate settings are sent to the master and scales.
n
The bus termination is either absent or is present multiple times. Check the wire jumpers
in the connection plug. See chapter ‘XES3 Serial Interface’ for details.
n
The timeout parameter has been set too low. Change the parameterization of the scales.
n
An improper ID has been identified in the telegram from the master to the scales.
See the section on error codes
16.11 EasyServe Fieldbus view
The chapter ‘Fieldbusses User Data Diagnosis’ shows and explains how cyclical user data
is displayed for all protocols.
Modbus 16.11 EasyServe Fieldbus view
INTECONT® Satus Operating Manual BV-H2346GB / 0833 81
© Schenck Process

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Schenck process Intecont Satus and is the answer not in the manual?

Schenck process Intecont Satus Specifications

General IconGeneral
BrandSchenck process
ModelIntecont Satus
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals