17.3.5 ‘Communication Host’ (S9) event message
The event message is a group message for all errors concerning the Fieldbus connection.
These are:
n
Different station addresses are sent to the master and scales.
n
Fieldbus cable is not working or improperly connected. See the chapter ‘Fieldbus Hard
-
ware’ for the correct connection.
n
The timeout parameter has been set at too small a value. Change the parameterization
of the scales.
See the section on error codes
Monitoring the Fieldbus channels
The Fieldbus channels are monitored for timeout. Timeout and all Modbus errors are
registered as ‘Communication Host (S9)’ event messages.
In the terms of this monitoring strategy, EasyServe is not considered to be a Fieldbus client.
The special settings in the relevant parameter block apply for EasyServe and also the same
rules with regard to logging on and off apply as with a serial coupling.
17.3 Modbus/TCP Ethernet
86 BV-H2346GB / 0833 Operating Manual INTECONT® Satus
© Schenck Process

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Schenck process Intecont Satus and is the answer not in the manual?

Schenck process Intecont Satus Specifications

General IconGeneral
BrandSchenck process
ModelIntecont Satus
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals