14.4 Proficbus DP master settings
Device log file (GSD)
of the INTECONT
® Satus is a Compact Device.
Note:
n
The configuration of the INTECONT® Satus can be found in the S7 hardware configura
-
tor under ‘Profibus DP/Other field devices/Controller/INTECONT® Satus’.
n
The current ISA10A98.GSD GSD file can be downloaded from the Schenck-Process
GmbH service website (http://support.schenckprocess.com, path: Service-Download-Bus
System-Profibus)
n
When reading or writing double words in S7 systems: please note that the INTECONT®
Satus double words cannot be read or written with the S7 system function modules
SFC14 or SFC15. In this situation please use direct peripheral access!
14.5 Diagnosis and Troubleshooting
If one of the Fieldbusses has been activated (selected), every fault will be registered by the
‘’Communication Host’ (S9) event message if this message has not been assigned the event
class IG(NORE). The message is visible in the display and in EasyServe. If you only have a
display available, please read the following two sections, otherwise EasyServe will send
more information for error diagnosis.
Meaning of the ‘Communication Host’ S9 event message
The event message is a group message for all errors concerning the Fieldbus connection.
These are:
n
Different station addresses are sent to the master and scales.
n
There is a problem with the cabling between Fieldbus connection and main board. Ob-
serve the LEDs on the connection. If in doubt, turn the power off and on, if the paramete
-
rization has been performed correctly the connection will be initialized (red LED blinks).
n
Fieldbus cable is not working or improperly connected. See the chapter ‘Fieldbus Hard
-
ware’ for the correct connection.
n
The bus termination is either absent or is present multiple times. Check the resistances
at the connection (delivery condition is ‘not activated’) and possibly the resistances in the
bus plugs. See the chapter ‘Fieldbus Hardware’ for details.
n
The selected protocol does not correspond to the add-on card. Change the parameteri
-
zation or swap the interface connection.
n
The timeout parameter has been set at too small a value. Change the parameterization
of the scales.
n
The configuration of the scales does not correspond with the configuration of the master.
Change the incorrect GSD module or the parameterization of the scales.
n
An improper ID has been identified in the telegram from the master to the scales (use
only IDs printed in bold type!)
n
The release bit must always be set!
PROFIBUS DP 14.5 Diagnosis and Troubleshooting