Safety and Functional Tester GLP2-i/e
During the test, test object and test leads must not be touched!
The safety measures required by law must be adhered to!
Schleich GmbH * D-58675 Hemer * 0049 / (0)2372 / 9498-0 * 0049 / (0)2372 / 9498-99 *
http://www.schleich.com * info@schleich.com 8
1.2.4 Function test
The function test is either 1-phase or 3-phase. The operating manual deals with the standard variants. For
the accuracy of function tests that are not indicated here, please refer to our offer.
Function test, 1-phase:
Test voltage: 230V 1-phase AC potential-free
Test voltage fluctuation: depending on mains supply
Voltage measuring range: 260 Veff AC, DC
Resolution: 0.1 V
Measuring: TRMS
Test voltage for leakage current: 230V +10%
Current measuring range: 0 ... 2(5, 10, 16) A AC
Resolution: 0.01 A
Accuracy: 0.25% of measuring range
Measuring: TRMS
Set values: 0.01 ... 2A - freely programmable
Correction: with mathematical correction of the current consumption
in case of mains voltage fluctuations, connectable
Apparent - active power measuring range: 0... 1150VA (W)
Resolution: 1 VA (W)
Accuracy: 1% of measuring range
Correction: with mathematical correction of the power in case of mains
voltage fluctuations, connectable
cosPhi measuring range: 0...1
Resolution: 0.01
Test time: 0.1 seconds ... 24 hours - freely programmable
Starting time: freely programmable
Short-circuit test: before and during the function test
Display: continuous display of voltage and current during the test
Tolerances: in +% and -% or as +limit value and -limit value
Function test, 3-phase:
Test object : 1-phase or 3-phase
Test voltage: 400V AC 3-phase current (mains voltage)
Voltage measuring range: 250Veff AC against neutral lead
Resolution: 1V
Measuring: TRMS / measured per phase
Current measuring range: 0 ... 16A AC
Resolution: 0.01A
Accuracy: 0.5% of measuring range
Measuring: TRMS / measured per phase
Set values: 0.1 ... 16A freely programmable
Test methods: current consumption, apparent power (between two phases), active power (between two
phases), cosPhi
cosPhi test: 0...1 / measured per phase
Resolution: 0.01
Test time: 0.1 seconds ... 24 hours - freely programmable
Short-circuit test: before and during the function test