It is technically possible and permitted to switch the relay contact manually. But if a
breaker should be connected directly to a DiggiMEC output relay, it would be opened
by such a manual switching, and the WIC1 would not be able to detect this. This
makes the whole protection concept unsafe and not permissible.
The WIC1 Backup Protection cannot switch a DiggiMEC output relay. It only uses the
“TC+/−” output.
118 WIC1 WIC1-1.0-EN-MAN
3 Hardware
3.9.2 DiggiMEC Connectors