37
4
Installing the DHF21B/41B option
Assembly and Installation Notes
LED L16
(Mod/Net)
The function of LED L16 (Mod/Net = Module/network state) described in the following
table is specified in the DeviceNet specification.
LED L15 (PIO) LED L15 (Polled I/O) monitors the polled I/O connection.
State of the
L16 LED
State Meaning
Off Not switched on/offline Unit is offline
Unit performs DUP MAC check
Unit is switched off
Flashing
green
(1 s cycle)
Online and in operational
mode
The unit is online and no connection has been
established
DUP-MAC check performed successfully
A connection has not yet been established with a
master
Missing, incorrect or incomplete configuration
Lights up
green
Online, operational mode
and connected
•Online
Connection to a master has been established
Connection is active (established state)
Flashing red
(1 s cycle)
Minor error or connection
timeout
A correctable error has occurred
Polled I/O and/or bit strobe I/O connections are in
timeout state
DUP-MAC check has detected an error
Red light Critical error or critical link
failure
A correctable error has occurred
•BusOff
DUP-MAC check has detected an error
State of the
L15 LED
State Meaning
Flashing
green
(125 ms
cycle)
DUP-MAC check Unit is performing DUP-MAC check
Off Not switched on/offline but
not DUP-MAC check
Unit is offline
Unit is switched off
Flashing
green
(1 s cycle)
Online and in operational
mode
Unit is online
DUP-MAC check performed successfully
A polled IO connection is being established with a
master (configuring state)
Missing, incorrect or incomplete configuration
Lights up
green
Online, operational mode
and connected
•Online
A polled I/O connection has been established
(established state)
Flashing red
(1 s cycle)
Minor error or connection
timeout
Invalid baud rate setting via DIP switches
A correctable error has occurred
Polled I/O connection is in timeout state
Red light Critical error or critical link
failure
An error that cannot be corrected has occurred
•BusOff
DUP-MAC check has detected an error