69
6
Diagnostic procedure CAN 1/CAN 2 system bus
Error Diagnostics
6 Error Diagnostics
6.1 Diagnostic procedure CAN 1/CAN 2 system bus
Diagnostic problem: Communication via system bus CAN 1 or CAN 2 does not work.
Initial status:
System bus CAN 1 or CAN 2 is connected correctly.
Communication via system bus CAN 1 or CAN 2 is programmed.
Is the bus connector
plugged in?
No [A]
Yes
Response of the LEDs CAN
1 or CAN 2 state?
Orange
[B]
Green
[C]
Lights up or flashes red
System bus CAN 1 or CAN 2 is not operating
or communication of the system bus is faulty.
[A]
Check the set baud rate.
Baud rate OK? No [D]
Yes
Make sure that terminating resistors are connected
properly.
[A] Check the bus cabling.
[B] System bus CAN 1 or CAN 2 is being initialized.
[C] Bus communication is OK.
Check the application program.
[D] Correct the baud rate.