Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
65
5
Communication via Ethernet
Project Planning and Startup with MOVITOOLS
®
MotionStudio
5.5.5 Communication parameters for SMLP
The following table describes the communication parameters for SMLP:
5.5.6 Communication ports used
The following table describes the communication ports MOVITOOLS
®
MotionStudio
uses:
Communication parameters Description Note
Timeout Waiting time in ms that the client
waits for a response from the
server after it has made a
request.
• Default setting: 1000 ms
• Increase the value as
required if a delay in
communication is causing
malfunctions.
Broadcast IP address IP address of the local network
segment within which the unit
scan is carried out.
In the default setting, the unit
scan only detects units that are in
the local network segment.
IP address of SMLP server IP address of the SMLP server or
of other units that are to be
included in the unit scan but are
outside the local network
segment.
• Enter the IP address of units
that are to be included in the
unit scan but are outside the
local network segment.
• Enter the IP address of the
SIMATIC S7 control, if you
are operating an indirect
Ethernet to PROFIBUS
communication via SIMATIC
S7.
Excluded IP address IP addresses of units that should
not be included in the unit scan
Enter the IP address of units that
should not be included in the unit
scan. This can be units that are
not ready for communication (for
example because they have not
been started up yet)
Application No. of communication
port
Description
ETH server 300 For using a PC as Ethernet gateway with
the program "ETHServer.exe"
SEW communication server 301 For communication between
MOVITOOLS
®
MotionStudio and the
SEW Communication Server
Offline data server 302 For communication of
MOVITOOLS
®
MotionStudio in offline
mode
MOVIVISION
®
server 303 For communication with a PC with active
MOVIVISION
®
server
MOVI-PLC
®
visualization 304 For communication between MOVI-PLC
®
and the 3D simulation of
MOVITOOLS
®
MotionStudio
TCI server 305 For communication via TCI
EcEngineeringServer remote
control (in preparation)
306 For direct communication (without master)
with SEW EtherCAT slaves
EcEngineeringServer mailbox
gateway (in preparation)
307 For direct communication (without master)
with SEW EtherCAT slaves