EasyManua.ls Logo

SEW-Eurodrive DHE21B - DHF21 B;41 B Option

SEW-Eurodrive DHE21B
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
73
7
DHF21B/41B option
Technical Data and Dimension Drawings
7.3 DHF21B/41B option
INFORMATION
Connections identical with those of the DHE21B/41B option are described in the
"DHE21B/41B option" chapter.
DHF21B/41B option
Part number DHF21B: 1823 608 1
DHF41B: 1821 161 5
Electrical supply Installed in MOVIDRIVE
®
MDX61B:
Power consumption: P
max
= 8 W
Installed in the MOVIAXIS
®
master module (MXM):
Power consumption: P
max
= 10 W
Potential levels Option DHF21B/41B has the following potential levels:
Potential control / CAN 1 / COM1
Potential COM2
Potential binary inputs and outputs
Potential system bus CAN 2
Potential PROFIBUS
PROFIBUS connection
X30P:1 X30P:9
via 9-pin sub D connector, pin assignment to IEC 61158
Bus termination Not integrated. Activate bus termination with suitable PROFIBUS connector with switchable terminating
resistors.
Automatic baud rate
detection
9.6kBd–12MBd
DeviceNet connection
X30D:1 X30D:5
2-wire bus and 2-wire supply voltage DC 24 V with 5-pole Phoenix terminal
Pin assignment according to DeviceNet specification
Baud rate 125, 250 or 500 kBaud, can be set using DIP switches 2
6
and 2
7
Bus cable length For thick cable according to DeviceNet specification 2.0 appendix B:
500 m at 125 kBd
250 m at 250 kBd
100 m at 500 kBd
MAC ID 0 – 63, can be set using DIP switch 2
0
– 2
5
Max. 64 stations
Engineering Additional engineering access via the PROFIBUS interface (X30P)
P
i
f
kVA
Hz
n