Operating Instructions Chapter 5
C4000 Micro/Basic/Basic Plus/Eco
8009423/YT79/2016-03-14 © SICK AG • Industrial Safety Systems • Germany • All rights reserved 29
Subject to change without notice
Electrical installation
5 Electrical installation
Switch the entire machine/system off line!
The machine/system could unintentionally start up while you are connecting the devices.
Ensure that the entire machine/system is disconnected during the electrical installa-
tion.
Ensure that downstream contactors are monitored!
Downstream contactors must be positively guided and monitored (see section 5.4 “Exter-
nal device monitoring (EDM)” on page 33)!
Connect OSSD1 and OSSD2 separately!
You are not allowed to connect OSSD1 and OSSD2 together, otherwise signal safety will
not be ensured.
Ensure that the machine controller processes the two signals separately.
a
WARNING