Speed
•
R
ange: The monitoring case is activated if the speed is within the specified range.
You can use static control inputs as additional input conditions.
•
Limit: The monitoring case is activated via the static control inputs. The safety laser
scanner monitors the speed. If the speed is outside the specified range, the safety
laser scanner switches the safety outputs to the OFF state.
In this mode, the safety laser scanner ignores different speeds of the two incre‐
ment
al encoders for 60seconds, even if the difference is greater than the config‐
ured tolerance.
Complementary information
The Generate input conditions function allows you to automatically assign input conditions
to monitoring cases.
7.15.5 Cut-off paths
You can create cut-off paths and define the outputs switched by the cut-off paths.
Y
ou need a cut-off path for every field in a field set. If the field sets have different sizes,
use the field set with the most fields as a guide.
Creating cut-off path and entering a name
1.
Create a cut-off path for every field in the largest field set.
2. Enter a descriptive name for each cut-off path.
Assigning the number of the cut-off path in the assembly
►
Select the desired number.
✓
The number is assigned to the cut-off path.
Restart behavior
You define the restart behavior for all network outputs in the Inputs and outputs window.
If needed, define a deviating restart behavior for one or several network outputs.
7.15.6 Assigning field sets
Overview
T
he field sets that have been created are listed in the Field sets area.
Procedure
A
ssign a field set to a monitoring case
►
Assign a field set to a monitoring case using drag and drop.
✓
The fields in a field set are arranged as they were drawn in the field editor.
Assigning a field to a monitoring case
1. Assign a field set to a monitoring case using drag and drop.
2. Right click on the assigned field set and select Split fieldset.
3. Assign the individual fields to one or various monitoring cases.
Removing assignment
►
Drag a field set or field from a monitoring case onto the trash can icon.
CONFIGURATION 7
8020200/1NTM/2024-06-03 | SICK O P E R A T I N G I N S T R U C T I O N S | microScan3 – EtherNet/IP™
125