6.2.1 microScan3 – EtherNet/IP™
Table 9: System plug and connections: microScan3 – EtherNet/IP™
Safety laser scanner Suitable system plug Plug connector
microScan3 – EtherNet/IP™
MICSX-BANNZZZZ1 (part number: 2086102)
•
XD1: v
oltage supply, page 86
•
XF1, XF2: 2 × network for
EtherNet/IP – CIP Safety, data
output, configuration, and diag‐
nostics, page 87
•
Alternative FE connection,
page 86
6.3 Pin assignment
You will find the pin assignment for the individual plug connectors in the following.
6.3.1 Voltage supply (XD1)
Voltage supply is supplied via a 4-pin, A-coding M12 male connector on the device side.
Figure 52: Pin assignment of the voltage supply (male connector, M12, 4-pin, A-coded)
Table 10: Pin assignment of the voltage supply
Pin Designation Function
1 24V DC 24VDC supply voltage
2 nc Not connected
3 0 V DC Supply voltage 0 V DC
4 FE Functional earth/shield
6.3.2 Alternative FE connection
Figure 53: Alternative FE connection
S
crew connection of the alternative FE connection
•
Screw: M5 × 12
•
Tightening torque: 3.5Nm to 5.0Nm
Suitable cable lugs
•
Forked cable lug or ring cable lug
•
Width ≤10mm
•
Hole diameter for screw: typically 5.2mm
Older system plugs (older than roughly September 2019) might not have an alternative
FE c
onnection.
6 ELE
CTRICAL INSTALLATION
86
O P E R A T I N G I N S T R U C T I O N S | microScan3 – EtherNet/IP™ 8020200/1NTM/2024-06-03 | SICK