13.8 Measurement data details
Table 54: Measurement data
Devices with a max. protective
f
ield range of 4.0m
Devices with max. protective
field range 5.5m
Devices with a max. protective
field range of 9.0m
Data output channels 1
Distance measurement range
1)
For remission factor = 10% ≤12m ≤22m
For remission factor =
100%
≤40m ≤64m
Scan rate
Scan cycle time 30ms 33Hz
Scan cycle time 40ms 25Hz 25Hz
Scan cycle time 50ms 20Hz
Angular resolution (physical)
2)
Scan cycle time 30ms <0.01°
Scan cycle time 40ms <0.01° <0.01°
Scan cycle time 50ms <0.01°
Angular resolution (safeHDDM®)
2)
Scan cycle time 30ms 0.51° (537 safeHDDM®
me
asured values)
Scan cycle time 40ms 0.39° (715 safeHDDM®
me
asured values)
0.125° (2,201 safeHDDM®
measured values)
Scan cycle time 50ms 0.1° (2,751 safeHDDM®
measured values)
Measurement uncertainty
3)
Systematic error ±10mm
Total measurement error (statistical and systematic)
At 1σ ±13mm ±18mm
At 2σ ±16mm ±26mm
At 3σ ±19mm ±34mm
At 4σ ±22mm ±42mm
At 5σ ±25mm ±50mm
1)
Warm-up time ≥30min. Light spot fully on the target object.
2)
safeHDDM® filters the physical measured values and provides very precise and reproducible measured
values. Only safeHDDM® measured values are available via data output.
3)
Typical values at 20°C and remission factor - 1.8%, distance = protective field range.
The measured values are less accurate for reflectors or reflective surfaces because the distance meas‐
urement is designed for lower remission values.
TECHNICAL DATA 13
8020200/1NTM/2024-06-03 | SICK O P E R A T I N G I N S T R U C T I O N S | microScan3 – EtherNet/IP™
183