The following system plugs are available for cascading:
S
ystem plug for single systems with an M12×4 + FE system connection (male con‐
nector)
System plug for cascaded systems with an M12×4 + FE system connection (male
connector) and an M12×4 + FE extension connection (female connector)
!
"
§
Figure 58: System plug with system connection
!
System plug
"
System connection
§
Device connection
!
$
"
§
Figure 59: System plug with system connection and extension connection
!
Extension connection
"
System plug
§
System connection
$
Device connection
Important information
DANGER
Ris
k of ineffectiveness of the protective device
The length of cable between 2 cascaded systems must not exceed 3 m.
b
Use the shortest possible cables between the devices of a cascaded system.
b
Protect the cascaded system from manipulation with an optimized length of cable
or with cable routing under a cover.
CONFIGURATION 7
8012624/10OM/2018-08-09 | SICK O P E R A T I N G I N S T R U C T I O N S | miniTwin4
69
Subject to change without notice