3UG4.1 line monitoring relay
6.5 3UG4614 line monitoring relay
3UG4 / 3RR2 monitoring relays
132 Manual, 05/2016, NEB927043002000/RS-AC/004
6.5.2
Functions
General functionality
The 3UG4614 line monitoring relays monitor a three-phase system for
phase asymmetry
,
undervoltage
,
phase failure
, and
phase sequence
.
The devices feature a wide-range voltage input and are
self-powered
(measuring voltage
= rated control supply voltage). The 3UG4614 line monitoring relays monitor all phases of
three-phase AC networks from 160 to 690 V through terminals L1 / L2 / L3 and also draw
power from all three phases simultaneously.
The 3UG4614 line monitoring relays feature 2 output relays (output relay K1 and output relay
K2). The relays work synchronously.
You will find the setting ranges and factory settings of the available parameters in Chapter
"Operation (Page 135)."
You will find a description of the individual parameters in Chapter "Parameters (Page 363)."
Note
The specified voltages represent the absolute thresholds.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 3UG4 and is the answer not in the manual?

Siemens 3UG4 Specifications

General IconGeneral
Type of voltageAC/DC
Number of CO contacts for auxiliary contacts1
Number of NC contacts delayed0
Number of NO contacts delayed0
Number of change-over switches delayed0
Number of NC contacts undelayed0
Number of NO contacts undelayed0
Number of change-over switches undelayed1
Width22.5 mm
Housing Width22.5 mm
Operating Temperature-25 ... 60 °C
Protection ClassIP20
Design of the productMonitoring relay
TypeMonitoring relay
Operating frequency rated value50 ... 60 Hz
Rated Operational Current0.1 ... 10 A
Adjustable response value current0.1 ... 10 A
Contact Configuration1 CO contact
Operating range factor control supply voltage rated value at AC0.8-1.1 x Un
Operating range factor control supply voltage rated value at DC0.8-1.1 x Un