3UG463. voltage monitoring relay
10.2 3UG4631 / 3UG4632 voltage monitoring relay
3UG4 / 3RR2 monitoring relays
Manual, 05/2016, NEB927043002000/RS-AC/004
273
10.2.2
Functions
General functionality
Depending on the setting, the 3UG4631 / 3UG4632 voltage monitoring relays are powered
with a rated control supply voltage of 24 V AC/DC or 24 to 240 AC/DC and monitor an AC
voltage or DC voltage at terminals IN and M of the device for
overshoot
(U▲) or
undershoot
(U▼) or in
range monitoring
(U▲ and U▼).
The 3UG4631 / 32 voltage monitoring relays have a display and are parameterized with
three keys.
You will find the setting ranges and factory settings of the available parameters in Chapter
"Operation (Page 278)."
You will find a description of the individual parameters in Chapter "Parameters (Page 363)."
Monitoring
The output relay K1 responds in accordance with the set relay switching behavior (closed-
circuit principle NC or open-circuit principle NO). The set tripping delay time starts if the
monitored voltage overshoots or undershoots the corresponding set threshold value. After
expiry of the tripping delay time, the output relay K1 changes the switching state. On the
display, the currently displayed measuring value and the symbol for undershoot or overshoot
flash.
An output change-over contact is available as a signaling contact.
If the rated control supply voltage is switched on and no monitoring voltage is yet present,
the display indicates 0.0 V and shows a symbol for voltage overshoot monitoring, voltage
undershoot monitoring, or range monitoring.
You will find the switching states of the output relay below in the section entitled "Function
diagrams" and in Chapter "Diagnostics (Page 279)."

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 3UG4 and is the answer not in the manual?

Siemens 3UG4 Specifications

General IconGeneral
Type of voltageAC/DC
Number of CO contacts for auxiliary contacts1
Number of NC contacts delayed0
Number of NO contacts delayed0
Number of change-over switches delayed0
Number of NC contacts undelayed0
Number of NO contacts undelayed0
Number of change-over switches undelayed1
Width22.5 mm
Housing Width22.5 mm
Operating Temperature-25 ... 60 °C
Protection ClassIP20
Design of the productMonitoring relay
TypeMonitoring relay
Operating frequency rated value50 ... 60 Hz
Rated Operational Current0.1 ... 10 A
Adjustable response value current0.1 ... 10 A
Contact Configuration1 CO contact
Operating range factor control supply voltage rated value at AC0.8-1.1 x Un
Operating range factor control supply voltage rated value at DC0.8-1.1 x Un