3UG4625 residual current monitoring relay with 3UL23 transformer
8.4 Operation
3UG4 / 3RR2 monitoring relays
202 Manual, 05/2016, NEB927043002000/RS-AC/004
Parameterization of the devices is possible locally using the display and the three keys.
The following table lists the adjustable parameter information for the 3UG4625 residual
current monitoring relay:
Table 8- 2 Parameter information, 3UG4625 residual current monitoring relays with digital setting
"RUN" Threshold for overshoot (I▲) 0.03 A 40.0 A Depending on the value,
1.0 A
Warning threshold for
overshoot (I!)
Depending on the value,
0.01 A or 0.1 A
"SET" Initialization (Init) ERR OK -- ERR
Tripping delay time (I▲Del)
"SET" Relay switching behavior
(closed-circuit principle NC /
open-circuit principle NO)
NC or NO -- NC
Note
Various parameters are deactivated by setting OFF.
The parameters are described in the Chapter "Parameters (Page 363)".
Menu-based operation is described in the Chapter "Menu-based operation (Page 39)".
The 3UL23 residual current transformers used cover the entire fault current range from
0.03 to 40 A in all sizes.
For more information on the technical data of 3UL23 residual current transformers see
Chapter "Technical data (Page 346)".