3UG458. insulation monitoring relay
9.3 3UG4581 insulation monitoring relay
3UG4 / 3RR2 monitoring relays
Manual, 05/2016, NEB927043002000/RS-AC/004
233
9.3.7
Technical data
Measuring circuit
3UG4581-1AW30
Type of voltage for monitoring
AC
Measurable line frequency
Hz 5060
Network leakage resistance
µF
10
Adjustable response value impedance
1
1 … 100
General technical details
3UG4581-1AW30
Product function
insulation monitor
Product function
isolation control
Yes
Product function defect storage
Yes
Type of voltage of the controlled supply voltage
AC/DC
Operating frequency rated value
Hz
15400
Control supply voltage
for DC rated value
V
24240
at 50 Hz at AC rated value
V
24240
at 60 Hz at AC
rated value
V
24240
Operating range factor control supply voltage rated value
for DC
0.85 1.1
Working range factor supply voltage rated value at 50 Hz
for AC
0.85 1.1
Working range factor supply voltage rated value at 60 Hz
for AC
0.85 1.1
Impulse voltage resistance rated value
V
6 000
Thermal current
of the contact-affected switching element
maximum
A
4
Protection class IP
IP20
Ambient temperature
during operating
°C
-25+60
Item designation according to DIN EN 61346-2
K
Item designation
according to DIN 40719 extendable after
IEC 204-2 according to IEC 750
K

Table of Contents