EasyManua.ls Logo

Siemens 3UG4 - Properties

Siemens 3UG4
410 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3RR2 current monitoring relays
4.3 Performance features of current monitoring relays
3UG4 / 3RR2 monitoring relays
50 Manual, 05/2016, NEB927043002000/RS-AC/004
4.3.2
Properties
Table 4- 5 Equipment of 3RR2 current monitoring relays
Feature
Benefit
3RR21 Basic,
analog setting
3RR22 Standard,
digital setting
Reset function
• Enables manual or automatic resetting of the
monitoring relay
• Resetting directly on the device or by
disconnect
ing and reconnecting the supply voltage
(remote reset)
✓ ✓
ON-delay time
• Enables motor starting without evaluation of the
starting current
• Can be used to monitor motors with lengthy
startup
0 s to 60 s 0 to 99 s
Tripping delay time
• Prevents frequent warnings and disconnection in
response to currents in the vicinity of the
thresholds
• Permits brief violations of thresholds during
operation
0 s to 30 s 0 s to 30 s
Operating and
indicating elements
• For setting thresholds and delay times
• For selectable functions
• For fast and selective diagnostics
• Display for permanent indication of measured
values
LEDs and rotary
buttons
Display and buttons
Integrated contacts
• Allow the system or process to be shut down in
the event of an irregularity
• Can be used to output signals
1 CO contact 1 CO contact
1 semiconductor
output

Table of Contents