3RR2 current monitoring relays
4.3 Performance features of current monitoring relays
3UG4 / 3RR2 monitoring relays
50 Manual, 05/2016, NEB927043002000/RS-AC/004
4.3.2
Properties
Table 4- 5 Equipment of 3RR2 current monitoring relays
Feature
Benefit
3RR21 Basic,
analog setting
3RR22 Standard,
digital setting
Reset function
Enables manual or automatic resetting of the
monitoring relay
Resetting directly on the device or by
disconnect
ing and reconnecting the supply voltage
(remote reset)
ON-delay time
Enables motor starting without evaluation of the
starting current
Can be used to monitor motors with lengthy
startup
0 s to 60 s 0 to 99 s
Tripping delay time
Prevents frequent warnings and disconnection in
response to currents in the vicinity of the
thresholds
Permits brief violations of thresholds during
operation
0 s to 30 s 0 s to 30 s
Operating and
indicating elements
For setting thresholds and delay times
For selectable functions
For fast and selective diagnostics
Display for permanent indication of measured
values
LEDs and rotary
buttons
Display and buttons
Integrated contacts
Allow the system or process to be shut down in
the event of an irregularity
Can be used to output signals
1 CO contact 1 CO contact
1 semiconductor
output