EasyManua.ls Logo

Siemens 3UG4 - Page 318

Siemens 3UG4
410 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3UG4651 speed monitoring relay
12.7 Technical data
3UG4 / 3RR2 monitoring relays
318 Manual, 05/2016, NEB927043002000/RS-AC/004
General technical details
3UG4651-..A..
3UG4651-..W..
Product function
RPM monitoring relay
Design of the display
LCD
Product function
• rotation speed monitoring
Yes
• standstill monitoring
No
• defect storage
Yes
• reset external
Yes
• self-reset
Yes
• manual RESET
Yes
• open-circuit or closed-circuit current principle
Yes
Starting time
after the control supply voltage has
been applied
ms 500
Number of outputs
• as contact-affected switching element
– safety-related
– delayed switching
0
– non-delayed
0
– for reporting function
– delayed switching
1
– non-delayed
0
• as contact-less semiconductor switching
element
– safety-related
– delayed switching
0
– non-delayed
0
– for reporting function
– delayed switching
0
– non-delayed
0
Response time
maximum
ms 100
Stored energy time at mains power cut minimum
ms
10
Relative metering precision
%
10
Precision of digital display
+/- 1 Digit
Relative repeat accuracy
%
1

Table of Contents