On-Line Operation UMSITRPDS3-1
November 2005
6-16
6.2.10 Select Measured Value to be Displayed
Mode 13 has three options:
Display output current in mA
Display output current in % (of the set measured range)
Display input pressure in engineering units selected in mode 14
To make a selection:
1. Press the M pushbutton to enable mode 13.
2. Press either arrow pushbutton to select the desired option.
3. Press the M pushbutton to save the selection.
6.2.11 Select the Displayed Input Pressure Engineering Unit
Mode 14 selects the engineering units that are to be assigned to the displayed input pressure (selected in
mode 13). Available selections are shown in Figure 6-3. The engineering unit set using HART (Section
6.4.11) has no effect on this local setting.
1. To select the engineering unit:
2. Press the M pushbutton to enable mode 14.
3. Press either arrow pushbutton to step through the available engineering units list.
4. Press the M pushbutton to save the selection.
If the capacity of the digital display is exceeded, 9.9.9.9.9 will appear.