EasyManua.ls Logo

Siemens CIM - Modbus RTU

Siemens CIM
125 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Web-based configuration
5.4 Web pages
CIM
70 Operating Manual, 11/2022, A5E51250518-AC
5.4.7.4 Modbus RTU
This page allows you enable, disable and set the Modbus RTU connection.
CIM supports only one Modbus RTU connection, either as Modbus RTU master or Modbus RTU
slave.
Enable or disable the Modbus RTU connection
Note: Modbus RTU connection is not secure.
Here you configure the properties of the connections of serial port.
Mode: RS485, RS422 or RS232
Baud-rate: set the transfer speed
Transmission: serial port setup
Terminal Resistor: enable or disable the embedded terminal resistor
Link to Modbus address space information page
Here you configure the Modbus RTU Type
If you select "Master", you need to set the "Data transfer table".
If you select "Slave", you need to set the "Modbus RTU Slave ID".
Range for the "Modbus RTU Slave ID": 1 to 255.

Table of Contents

Related product manuals