What to do if Siemens Inverter motor fails to run after changing the parameters?
- JJesse NicholsAug 23, 2025If the Siemens Inverter motor fails to run after changing the parameters, set P0010 = 30, then P0970 = 1, and press P to reset the inverter to the factory default parameter values. Alternatively, use a switch between terminals 5 and 8 on the control board; the drive should now run to the defined setpoint by analogue input. 