7 Operation at Use of a PC
7.5 Maintenance
175SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Click Browse....
The Choose File to Upload dialog opens.
Select the desired update (extension .pck) in the directory.
Click Open.
The selected path is inserted in the input/output window, Figure 7-61, into the Browse... field.
Click Open on the tab.
After approx. 2 s, the message Action was successful! is displayed in the input/output window.
Device firmware, default set of parameters, text libraries, HTML files or parts thereof are uploaded within
one minute.
The device then restarts automatically.
NOTE
If you want to carry out a firmware update, you must stop the record manually before., see Recording
Parameters.
Do not switch off the supply voltage during the upload process as this can lead to data loss.