8 Operation at Use of the Display
8.4 Parameterization
203SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Table 8-3 Basic Parameter Settings
Parameter Default Setting Setting Range
Voltage Inputs
Connection type The connection type is indicated on the display. However, it can be set via
the User interface only.
Rated value The rated value is indicated on the display. However, it can be set via the
User interface only.
Use PTs? No
(no checkmark)
Yes (checkmark)
No (no checkmark)
Use PTs:
V primary
Primary rated voltage Ph-Ph
AC 10,000.00 V AC 100.00 V to 1,000,000.00 V
Use PTs:
V secondary
Secondary rated voltage Ph-
Ph
AC 100 V AC 1.0 V to 1000.0 V
Current Inputs
Rated value AC 5 A AC 1 A
AC 5 A
Use CTs? No
(no checkmark)
Yes (checkmark)
No (no checkmark)
Use CTs:
I primary
primary rated current
AC 1,000.00 A AC 1.0 A to 100,000.0 A
Use CTs:
I secondary
secondary rated current
AC 1.00 A AC 0.01 A to 10 A
Zero-Point Suppression
Zero-point suppression
(in % of Vrated
and Irated)
0.3 % 0.0 % to 10.0 %