13 Operational Indications
240 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Daylight Saving Time Switching between daylight saving
time/standard time
Indication on: Daylight saving time
Indication off: Standard time
Ethernet Link Error Ethernet connection error Indication on: Error
Indication off: Ethernet link recognized
Modbus TCP OK
(Modbus TCP Server)
At least one Modbus TCP link has
received Modbus messages.
Indication on: At least one Modbus message was re-
ceived during the set monitoring time. The time stamp is
set when the first valid message is received.
Indication off: No Modbus message was received during
the set monitoring time.
See chapter 7.3.6.2
Settings Load Starting to change the parameters
of the passive set of parameters.
Indication on: Start of changes
Indication off: Changes complete
Settings Check The passive set of parameters is to
be activated; the internal parame-
ter check is running.
Indication on: Check started
Indication off: Check complete
Settings Activate The passive set of parameters is
enabled and the device works with
these parameters.
Indication on: Activation started
Indication off: Activation complete
Limit Violation x Indication that a parameterized lim-
iting value has been violated
Indication on: The limit of the monitored measured value
has been violated or no measured value is parameter-
ized as input of the limiting value.
Indication off: The limit of the monitored measured value
is not violated.
Message invalid: The monitored measured value is
invalid
(e.g. frequency at V < 15 % of V
rated
).
x = 1 to 16
Indication 1 from
Remote
Status of the indications that can
be set to control the LEDs and the
binary outputs via the communica-
tion.
Indication on: ON
Indication off: OFF
Message invalid: Not yet updated via the communication
or again invalid via the communication
Indication 2 from
Remote
Binary Output 1 Status of binary outputs ON/OFF Indication on: ON
Indication off: OFF
Only if not output as counter output
(for counter output = 0)
Binary Output 2
Reset Energy The energy counters were reset. Indication on: Energy counters reset
Indication Description Notes