13 Operational Indications
241SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
1) The SD card has no contact or is defective; you must not replace the card yourself. The device also works
without active SD card. However, data storage when operating the recorders is not possible. In this case,
the recorder data can be forwarded and processed only via communication.
Rotating Field Clock-
wise
Indication of rotation voltage Indication ON: Phase sequence Va-Vb-Vc, rotation
clockwise
Indication OFF: Phase sequence Va-Vc-Vb, (2 phases
interchanged); rotation anti-clockwise
Indication invalid: Direction of rotation can not calculated
(e.g. no voltage applied)
Group indication x Up to 4 single-point indications can
be linked logically and combined to
a group indication.
A total of 4 group indications (x = 1 to 4) can be param-
eterized.
Supply Voltage Event
Available
Indication of a supply voltage event Overvoltage, undervoltage, frequency interruption
Frequency Event
Available
Indication of a frequency event Overfrequency or underfrequency
Volt. Unbalance
Event Available
Indication of a voltage unbalance
event
Voltage unbalance
PQ Event Indication of a fault recorder event A fault record was recorded.
SD Card Error Indication of an SD card error SD card defective or read/write error
1)
Indication Description Notes