EasyManua.ls Logo

Siemens SENTRON PAC5200 - Page 30

Siemens SENTRON PAC5200
266 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Measurands and Recording
4.1 Measuring and Recording System
30 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Flicker
The short-term flicker value Pst and long-term flicker value Plt are determined for phase-to-ground volt-
ages and delta voltages. The flicker measurement is performed according to EN 61000-4-15.
The flicker measurement is performed on all 3 voltage channels.
Flickers appear with a frequency from 0.005 to 35 Hz. The instantaneous flicker value is displayed in per-
ceptibility units P.
Short-term flicker value Pst
determined over 10 min (short-term flicker), fixed
Long-term flicker value Plt
over 2 h (12 Pst values), fixed
Perceptibility Pinst

Table of Contents

Related product manuals